LECTURE ¹14
PNEUMATIC SYSTEMS. AIR
TREATMENT AND PRESSURE REGULATION
14.1. AIR TREATMENT STAGES
For satisfactory operation
of the pneumatic system the compressed air needs to be cleaned and dried.
Atmospheric air is contaminated with dust, smoke and is humid. These particles
can cause wear of the system components and presence of moisture may cause
corrosion. Hence it is essential to treat the air to get rid of these
impurities. The air treatment can be divided into three stages as shown in
Figure 14.1.1.
Fig. 14.1.1. Stages of air
treatment
In the first stage, the
large sized particles are prevented from entering the compressor by an intake
filter. The air leaving the compressor may be humid and may be at high
temperature. The air from the compressor is treated in the second stage. In
this stage temperature of the compressed air is lowered using a cooler and the
air is dried using a dryer. Also an inline filter is provided to remove any
contaminant particles present. This treatment is called primary air treatment.
In the third stage which is the secondary air treatment process, further
filtering is carried out. A lubricator introduces a fine mist of oil into the
compressed air. This will help in lubrication of the moving components of the
system to which the compressed air will be applied.
Filters
To prevent any damage to the
compressor, the contaminants present in the air need to be filtered out. This
is done by using inlet filters. These can be dry or wet filters. Dry filters
use disposable cartridges. In the wet filter, the incoming air is passed
through an oil bath and then through a fine wire mesh filter. Dirt particles
cling to the oil drops during bubbling and are removed by wire mesh as they
pass through it. In the dry filter the cartridges are replaced during
servicing. The wet filters are cleaned using detergent solution.
Cooler
As the air is compressed,
the temperature of the air increases. Therefore the air needs to be cooled.
This is done by using a cooler. It is a type of heat exchanger. There are two
types of coolers commonly employed viz. air cooled and water cooled. In the air
cooled type, ambient air is used to cool the high temperature compressed air,
whereas in the water cooled type, water is used as cooling medium. These are
counter flow type coolers where the cooling medium flows in the direction
opposite to the compressed air. During cooling, the water vapor present will
condense which can be drained away later.
14.2. MAIN LINE
FILTER
These filters are used to
remove the water vapors or solid contaminants present in the pneumatic systems
main lines. These filters are discussed in detail as follows.
Air filter and
water trap
Air filter and water trap is
used to:
·
prevent any
solid contaminants from entering in the system;
·
condense and
remove water vapor that is present in the compressed air.
Fig. 14.2.1. Air filter and
water trap
The filter cartridge is made
of sintered brass. The schematic of the filter is shown in Fig. 14.2.1. The
thickness of sintered cartridge provides random zigzag passage for the air to
flow-in which helps in arresting the solid particles. The air entering the
filter swirls around due to the deflector cone. The centrifugal action causes
the large contaminants and water vapor to be flung out, which hit the glass
bowl and get collected at the bottom. A baffle plate is provided to prevent the
turbulent air from splashing the water into the filter cartridge. At the bottom
of the filter bowl there is a drain plug which can be opened manually to drain
off the settled water and solid particles.
Refrigerated
dryers
Fig. 14.2.2. Refrigerated
dryers
It consists of two heat
exchangers, refrigerant compressor and a separator. The system circuitry is
shown in Figure 14.2.2. The dryer
chills the air just above 0 °C which condenses the water vapor. The condensate
is collected by the separator. However such low temperature air may not be
needed at the application. Therefore this chilled air is used to cool the high
temperature air coming out from the compressor at heat exchanger 2. The
moderate temperature dry air coming out from the heat exchanger 2 is then used
for actual application; whilst the reduced temperature air from compressor will
further be cooled at heat exchanger 1. Thus, the efficiency of the system is
increased by employing a second heat exchanger.
14.3. LUBRICATORS
Fig. 14.3.1. Air lubricator
The compressed air is first
filtered and then passed through a lubricator in order to form a mist of oil
and air to provide lubrication to the mating components. Figure 14.3.1 shows
the schematic of a typical lubricator. The principle of working of venturimeter
is followed in the operation of lubricator. The compressed air from the dryer
enters in the lubricator. Its velocity increases due to a pressure differential
between the upper and lower changer (oil reservoir). Due to the low pressure in
the upper chamber the oil is pushed into the upper chamber from the oil
reservoir through a siphon tube with check valve. The main function of the
valve is to control the amount of oil passing through it. The oil drops inside
the throttled zone where the velocity of air is much higher and this high
velocity air breaks the oil drops into tiny particles. Thus a mist of air and
oil is generated. The pressure differential across chambers is adjusted by a
needle valve. It is difficult to hold an oil mixed air in the air receiver as
oil may settle down. Thus air is lubricated during secondary air treatment
process. Low viscosity oil forms better mist than high viscosity oil and hence
ensures that oil is always present in the air.
14.4. PRESSURE REGULATION
In pneumatic systems, during
high velocity compressed air flow, there is flow-dependent pressure drop
between the receiver and load (application). Therefore the pressure in the
receiver is always kept higher than the system pressure. At the application
site, the pressure is regulated to keep it constant. There are three ways to
control the local pressure, these are shown in Figure 14.4.1.
Fig. 14.4.1. Types of pressure regulation
·
In the first
method, load X vents the air into atmosphere continuously. The pressure
regulator restricts the air flow to the load, thus controlling the air
pressure. In this type of pressure regulation, some minimum flow is required to
operate the regulator. If the load is a dead end type which draws no air, the
pressure in the receiver will rise to the manifold pressure. These type of regulators
are called as «non-relieving
regulators», since the air
must pass through the load.
·
In the second
type, load Y is a dead end load. However the regulator vents the air into
atmosphere to reduce the pressure. This type of regulator is called as «relieving regulator».
·
The third type
of regulator has a very large load Z. Therefore its requirement of air volume
is very high and can’t be fulfilled by using a simple regulator. In such cases,
a control loop comprising of pressure transducer, controller and vent valve is
used. Due to large load the system pressure may rise above its critical value.
It is detected by a transducer. Then the signal will be processed by the
controller which will direct the valve to be opened to vent out the air. This
technique can be also be used when it is difficult to mount the pressure
regulating valve close to the point where pressure regulation is needed.
14.5. RELIEF VALVE
Relief valve is the simplest
type of pressure regulating device. The schematic of its construction and
working is shown in the Figure 14.5.1. It is used as a backup device if the
main pressure control fails. It consists of ball type valve held on to the
valve seat by a spring in tension. The spring tension can be adjusted by using
the adjusting cap. When the air pressure exceeds the spring tension pressure
the ball is displaced from its seat, thus releasing the air and reducing the
pressure. A relief is specified by its span of pressure between the cracking
and full flow, pressure range and flow rate. Once the valve opens (cracking
pressure), flow rate depends on the excess pressure. Once the pressure falls
below the cracking pressure, the valve seals itself.
Fig. 14.5.1. Relief valve
Service units
During the preparation of
compressed air, various processes such as filtration, regulation and
lubrication are carried out by individual components. The individual components
are: separator/filter, pressure regulator and lubricator. Preparatory functions
can be combined into one unit which is called as «service unit». Figure 14.5.2 shows symbolic representation of various processes
involved in air preparation and the service unit.
Fig. 14.5.2. Service unit components and service unit symbol